1、变压器试验报告安装位置古浪1#变压器试验性质交接型号SFZl1-63000/110试验日期2015.8.25额定电压(KV)高压110额定电流(A)高压/低压10.5低压/额定容量(KVA)63000短路阻抗(%)10.31联接组别YNdll空载损耗(KW)34.84负载损耗(KW)216.49空载电流(%)0.07冷却方式ONAN出厂日期2014.09出厂编号2014012制造厂家宁波天安变压比试验分接开关位置高压侧/低压侧实测变压比变压比误差()ABZabBC/bcCA/caAB/abBC/bcCA/ca19.4319.4309.431+0.02+0.01+0.0229.5639.5629
2、.562+0.03+0.02+0.02311.27511.27411.274+0.11+0.10+0.10411.14311.14311.143+0.10+0.10+0.10511.01111.01111.011+0.09+0.09+0.09610.88110.87910.879+0.10+0.09+0.09710.74810.74710.747+0.09+0.08+0.08810.61610.61610.616+0.08+0.08+0.089a/Z/9b10.48510.48310.485+0.08+0.06+0.089c/1010.35410.35310.354+0.08+0.07+0.0
3、81110.22210.22110.222+0.07+0.06+0.071210.09010.09010.090+0.06+0.06+0.06139.9589.9579.958+0.05+0.04+0.05149.8279.8269.826+0.05+0.04+0.04159.6939.6949.695+0.02+0.03+0.041611.40711.40511.407+0.12+0.10+0.121711.53911.53811.538+0.13+0.12+0.12高压绕组直流电阻(Q)目别分接位直AOBOCO三相直流电阻不平衡率()10.28070.28180.28170.3920.27
4、620.27730.27710.4030.27180.27290.27270.4040.26730.26830.26820.3750.26290.26380.26370.3460.25830.25930.25920.3970.25390.25500.25480.4380.24940.25030.25020.369a/9b0.24420.24440.24460.169c/100.24910.24980.25010.40110.25370.25430.25470.39120.25820.25890.25930.43130.26290.26350.26390.38140.26740.26800.26
5、850.41150.27200.27270.27310.40160.27660.27720.27760.36170.28130.28190.28220.32低压绕组直流电阻(Q)abbeca三相直流电阻不平衡率()0.0034700.0034740.0034730.12绝缘电阻试验试部位项目高压对低压及地低压对高压及地高压对低压铁心对地测试时间60S/15S60S/15S60S/15S60S绝缘电阻(GU)25.80/19.5016.00/12.0028.10/20.5012.10吸收比()1.321.331.37/介质损失角试验试部位项目高压对低压及地低压对高压及地高压及低压对地Cx(Pf)
6、9594.013658.010383.0tg(%)(15)oC0.2260.2880.230tg(%)(20)C0.2600.3310.265耐压试验项目测试部位交流耐压直流耐压电压(KV)频率(HZ)时间(min)电压(KV)时间(min)泄漏电流(A)高压对低压及地1605014019低压对高压及地285011014备注结论试验人:变压器试验报告安装位置古浪2#变压器试验性质交接型号SFZl1-63000/110试验日期2015.8.25额定电压(KV)高压110额定电流(A)高压/低压10.5低压/额定容量(KVA)63000短路阻抗(%)10.23联接组别YNdll空载损耗(KW)33
7、.70负载损耗(KW)216.25空载电流(%)0.07冷却方式ONAN出厂日期2014.10出厂编号2014013制造厂家宁波天安变压比试验分接开关位置高压侧/低压侧实测变压比变压比误差()ABZabBC/bcCA/caAB/abBC/bcCA/ca111.53611.53511.536+0.10+0.09+0.10211.40511.40311.405+0.10+0.09+0.10311.27311.27211.273+0.10+0.09+0.10411.14211.14111.142+0.10+0.09+0.10511.01011.00911.010+0.09+0.08+0.09610.
8、87610.87910.878+0.06+0.09+0.08710.74710.74610.746+0.08+0.07+0.07810.61110.61410.617+0.03+0.06+0.099a/Z/9b10.48410.48310.483+0.07+0.06+0.069c/1010.35410.35310.354+0.08+0.07+0.081110.22310.22110.221+0.08+0.06+0.061210.09010.09110.087+0.06+0.07+0.06139.9589.9589.958+0.05+0.05+0.05149.8269.8289.827+0.04
9、+0.06+0.05159.6999.6959.695+0.08+0.04+0.04169.5639.5639.564+0.03+0.03+0.04179.4329.4319.432+0.03+0.02+0.03高压绕组直流电阻(Q)目别分接位直AOBOCO三相直流电阻不平衡率()10.29450.29560.29530.3720.28990.29110.29030.4130.28560.28660.28590.3540.28110.28220.28210.3950.27740.27830.27770.3260.27280.27390.27330.4070.26920.26930.26880.
10、1980.26500.26610.26570.419a/9b0.26090.26100.26040.239c/100.26590.26680.26640.34110.27010.27090.27070.30120.27450.27530.27470.29130.27820.27910.27910.32140.28260.28340.28350.32150.28760.28810.28780.17160.29180.29250.29250.24170.29730.29720.29860.47低压绕组直流电阻(Q)abbeca三相直流电阻不平衡率()0.0034260.0034270.003442
11、0.47绝缘电阻试验试部位项目高压对低压及地低压对高压及地高压对低压铁心对地测试时间60S/15S60S/15S60S/15S60S绝缘电阻(GU)19.90/14.9012.00/8.5020.90/12.1011.10吸收比()1.341.411.73/介质损失角试验试部位项目高压对低压及地低压对高压及地高压及低压对地Cx(Pf)9735.017787.06604.2tg(%)(15)oC0.2360.2560.242tg(%)(20)C0.27150.2940.278耐压试验项目测试部位交流耐压直流耐压电压(KV)频率(HZ)时间(min)电压(KV)时间(min)泄漏电流(A)高压对低压及地16050140167低压对高压及地2850110116备注结论试验人: